SECTION 16010 ELECTRICAL GENERAL PROVISIONS SECTION 16010 ELECTRICAL GENERAL PROVISIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under this Section. SECTION 16010 . This includes but is not limited to updating Equipment and/or Material Model Numbers indicated in the specifications and adding any additional specifications that may be required by the project. Provide an index chart for identification. % APPROVED EQUAL EQUIPMENT LAYOUTS Approved Equal Equipment Layouts: The equipment layouts and the related mechanical and electrical service connections, access space and supports indicated on the construction documents represent equipment provided by the specified basis of design manufacturer and model number. 571 0 obj <> endobj Supplementary Conditions and Division-1 Specification Sections, apply to this Section. 1820 0 obj <> endobj _^QD!;\m6~D#}g}F\jf#Mt2tNT%$PkQwJuhN)2>IL gVV[ NYo8 bT6&/"I9k8rq#|,p]UW.nD,e$#)GY9AV/8JWh(tsU T/! These cookies do not store any personal information. SECTION 16012 -- SUBMITTALS CONTRACTOR'S CERTIFICATION: Each submittal shall contain a certification stating that the . while working on energized systems in accordance with NFPA 70E. 16 ELECTRICAL SPECIFICATION INDEX Section 16000 Bid Opportunity No. ?\ 2j0D,xl>Kc2)b01UBu0% ## d X%XIL Browse Part Number 16010, Narrow Section Ball Bearings (16000, 16100) in the The Timken Company catalog including Part Number,Item Name,Description,Clearance,Bore Size d,Features,Outside Diameter D,Outside Ring Width B,Radius Rs min,Cr - Dynamic Load Existing Construction: All new service penetrations through existing rated assemblies shall be provided with a pipe sleeve and sealant materials. Power Distribution System. 5. The lighting design shall have a cross-section of 2,5 mm and a circuit breaker of (1 x 10 A + N) - Minimum wire size shall be 2.5 mm. containing a completed specification Section 17015 will be automatically considered unresponsive and will be rejected. &%`T$cf:A5H(3Jy?'- ] 2 0 obj State of Maryland Fire Prevention Code. END OF SECTION 260000 University of Maryland, Baltimore Bressler Research Building Seventh Floor Renovation Project No. Job site and worker safety are the responsibility of the contractor. endstream endobj 265 0 obj<> endobj 266 0 obj<>/Encoding<>>>>> endobj 267 0 obj<> endobj 268 0 obj<>/ProcSet[/PDF/Text]/ExtGState<>>> endobj 269 0 obj<> endobj 270 0 obj<> endobj 271 0 obj<> endobj 272 0 obj<> endobj 273 0 obj<> endobj 274 0 obj<> endobj 275 0 obj<> endobj 276 0 obj<>stream 0000002433 00000 n Time of instruction shall be designated by the Owner. Maximum length: (six 6) feet, except where fished. ` I <> Machine name and specification section number of driven machine. Complete inventory of spare parts and materials. English Deutsch Franais Espaol Portugus Italiano Romn Nederlands Latina Dansk Svenska Norsk Magyar Bahasa Indonesia Trke Suomi Latvian Lithuanian esk . %%EOF Specifications and Drawings are prepared in abbreviated form and includes incomplete sentences. If installers are not experienced in procedures, provide instruction by manufacturer's representatives. %%EOF trailer NECA (National Electrical Contractors Association). Shutdown. C. %%EOF Comply with the following requirements: Coordinate electrical systems, equipment, and materials installation with other building components. L1)Tj4d v"1s%H"r$-j` ,}# A. Clean surfaces that come into contact with grout. Place markers in corner of tile. Product data as specified in the electrical specifications unless otherwise noted: Warranties and maintenance instructions shall be included in the O & M Manual only. Reference letters from minimum of three (3) registered professional engineers, general contractors, building owners, explaining proficiency, quality of work, or other attribute on projects of similar size or substance. Using the UMB Standard O&M Manual Template referenced in Division 01 Closeout Procedures insert the submittal files include both a bookmark and tree structure for accessing each submittal file in the manual. mHs00\%Q` Samples shall indicate applicable specification section number and item numbers within that section. Concrete shall be 3,500 psi twenty-eight (28) day compressive strength concrete and reinforcement bars as specified in the architectural specifications. An electrical foreman, superintendent or other supervisor familiar with the project shall be in attendance for all scheduled electrical inspections. Distribution panels. Only one submission per System Integrator will be allowed. 1835 0 obj <>/Filter/FlateDecode/ID[<436FD37774A5B745BAA68B131E232EA6>]/Index[1820 93]/Info 1819 0 R/Length 81/Prev 195435/Root 1821 0 R/Size 1913/Type/XRef/W[1 2 1]>>stream Provide acoustical caulking to seal the annular spaces between the sleeve and the bare pipe or pipe insulation on each end with one half (1/2) inch caulking all around the annular space. Patch holes and penetrations in wood, masonry and plaster. "$u D2iH>`:\ &Ea . Noise and vibration adjustments. Provide service and operating manuals for the following: Division 28 Section Digital, Addressable Fire Alarm System. %PDF-1.6 % ?Cc\C,Ns[Tj*I3t3kZ pd(68 Ulz %PDF-1.6 % hSmk0+q7Pt%i!4GK~ ?lat"=Ye vydw \CnnXVmTG.1IgFb3muJ M6[]\.I!M{S}/Upc_Ov>Il/tc@U(Bvf-+u=oga$a #c.OyY7;njc dQ)lvy 7J As]S97}y9/7Qu{w}Sc1^~w/(omZB;.2 }@qQ Mg=?X2Wqg?p0O/&swW7qrdS&~ `Owe ]NXzN&~hQE2vJcU#BgO# E Section 16050 - Basic Electrical Materials and Methods . Arrange for each installer of equipment that requires regular maintenance to meet with the Owner's personnel to provide instruction in proper operation and maintenance. EN. Each section of raceway must contain an equipment grounding wire bonded at each end and sized as required. CA-1817 / PN15160009 16010 - 1 DIVISION 16 - ELECTRICAL SECTION 16010 - GENERAL ELECTRICAL PROVISIONS PART 1 - GENERAL 1.01 INTENT OF SPECIFICATIONS AND DRAWINGS A. Install electrical equipment to facilitate servicing, maintenance, and repair or replacement of equipment components. 11261 0 obj <> endobj Energized electrical conductors and circuit parts to which an employee might be exposed shall be put into an electrically safe work condition before an employee performs work any time the employee is within the limited approach boundary or, where an increased risk of injury from an exposure to an arc flash hazard exists. Shut down. %PDF-1.5 % hb```,G@(b``oI Refer to Division 01 Section "Definitions and Standards" for definition of "experienced Installer." 0 F. Supply Voltage All existing unsealed penetrations for services passing through existing rated assemblies within the project area shall be provided with sealant materials. Clean each surface or unit to the condition expected in a normal, commercial building cleaning and maintenance program. CLOSEOUT PROCEDURES Operating and Maintenance Instructions: Submit Complete Package At Least Two (2) Months Prior To Substantial Completion. It shall be the responsibility of the Installer to obtain all necessary data from the equipment supplied under other Divisions. DIVISION 16 SECTION 16010 ELECTRICAL BASIC ELECTRICAL MATERIALS AND METHODS 16010 - 1 PART 1 - GENERAL 1.01 CONTRACT DOCUMENTS A. CUTTING AND PATCHING General: Perform cutting and patching in accordance with Division 1 Section "Cutting and Patching." 0000000596 00000 n The Architect/ Engineer will not perform any punch list verification until all items have been completed, initialed, dated and the list returned to the Architect/Engineer. This website uses cookies to improve your experience while you navigate through the website. Before shipment, the power distribution panel boards, shall be tested to ensure proper operation and conformance with manufacturer's published specifications. @ B F G c h j ~~vi^S~Hh"S{ h0$n CJ aJ hf h;F B* With super-finished raceways and controlled geometries, our premium design helps ensure consistent quality. M0*``mvle}vw$ms3s%)[Fpk, V7#`,kzp:dM b([0.@Sk8@KGq4EY2:":@DD L'czU4,f53( iX 89 The contractor shall include in his price the cost of all premium time required for outages and other work which interferes with the normal use of the building, which will be performed, in most cases, during other than normal work time and at the convenience of the University. Remove conduit, hangers, supports, etc. For compressorized equipment include an additional three (3) year Guarantee/Warranty Period. Use operation and maintenance manuals and video as basis of instruction. Housekeeping Pads: Pads shall be minimum of four (4) inches wider and longer than structural base of equipment being set on pad. Comply with manufacturer's instructions. NJ j5)'~# 4"{:k[k%nK0Er`@ Design Mix: 5,000psi (34.50MPa), twenty eight (28) day compressive strength. In default thereof, owner may have such work done and charge the cost of same to the contractor. This section is a Division-16 basic Electrical Materials and Methods section, and is part of each Division-16 section making reference to electrical raceways . Obtain all necessary permits from 0000001525 00000 n PROJECT OPERATION AND MAINTENANCE MANUAL ELECTRONIC FILES Project O & M Manual File: The project OM Manual shall include one (1) electronic copy of each approved submittal and any manufacturers maintenance manuals, and all warranty certificates included in Divisions 26, 27, & 28. 0 2020 0 obj <>stream Include a detailed review of the following items: Maintenance manuals, including a customized list of preventive maintenance items and annual schedule for maintenance. Related Specification Sections include, but are not limited to, the following: 1. (Engineer shall edit specifications and blue text in header to meet project requirements. ph p haP haU B*ph haP h8 B*ph haP haP B*ph h B*ph h"p B*ph h& B*ph hlg B*ph h+V B*ph h"S{ ho h"S{ h9}- h{\V h8 h[P h8 h9}- h8 h#y h"S{ h#y / j }H5@Gj\/vLBh@.\=r+TKi3Eg:xI=V{ T`WiRcfJ1Et*kIPd$ItI}J&]IES&IKO>Snv! %%EOF .2 Section 01810 -Commissioning. See Specification Division 01 for general requirements. 434-2007 Page 1 of 1 _____ INDEX OF SPECIFICATION 16010 Electrical, General Requirements 16122 Electrical, Wire and Cable 16133 Electrical, Conduits and Fittings 16225 Electrical, Control Panel . shall meet the requirements of the associated spec section(s). Samples shall indicate applicable specification %%EOF Access doors. 1.08 TESTING A. See underlined texts for Edits. PROVISIONS FOR ACCESS Furnish and install adequate access to all electrical components. Approved substitutions, Contract Modifications, RFI responses and actual equipment and materials installed. XB^c*x=.l0 r Remove conduit, hangers, supports, etc. SECTION 16010 - GENERAL PROVISIONS. In addition to the following list, submit other shop drawings as may be requested by UMB: Divisions 26, 27, & 28: Compression Wire Connectors Fire Resistant Sealant Ground Wire Surface Raceway Wireways Raceway, Boxes and Cabinets Wires and Cables Fire Alarm System: Refer to Division 28 Section Digital, Addressable Fire Alarm System for submittal requirements In instances of complex field wired systems, including but not limited to: fire alarm system, the contractor shall submit: Cut sheets of every component such as control panels, fire alarm devices, wire, etc. The following list shall be used as a guide only: Equipment such as transformers, generators, etc. HSMo@Wq~HU8 jPYqz0NAjFgvlwv=~|vjj*5MY}n`yQ?aLu:#heF{L[}:n! /C\_7sHsuHp$c1X?So0u*dMLeqi81cx,B2@(@>Nde7a-KZi:%A o#=drlbI6. Indicate locations where space is limited for installation and access and where sequencing and coordination of installations are of importance to the efficient flow of the Work, including (but not necessarily limited to) the following: Indicate the proposed locations of electrical equipment, and materials. !y-P+O`_ )q|ero-UPO]GmlQ^+RDdi*>Z o endstream endobj 11265 0 obj <>stream It is mandatory to procure user consent prior to running these cookies on your website. 0000001264 00000 n #Zkh f9\!A>V=#JM;:Dw. Corresponding floor plans showing only this particular system with conduit and wire runs between points. <> Coordination Drawings: In addition to the requirements of the Specification Division 01 prepare the plumbing part for the coordination drawing effort. SECTION 16010 - BASIC ELECTRICAL REQUIREMENTS SECTION 16111 - CONDUITS SECTION 16118 - DUCTBANK SECTION 16121 - MEDIUM VOLTAGE CABLE SECTION 16123 - BUILDING WIRES AND CABLES SECTION 16130 - BOXES SECTION 16140 - WIRING DEVICES SECTION 16160 - ENCLOSURES SECTION 16170 - GROUNDING AND BONDING SECTION 16180 - EQUIPMENT WIRING SYSTEMS SECTION 16190 301 and Section 16010 of these Specifications. SITE VISIT Prior to preparing the bid, the electrical subcontractor shall visit the site and become familiar with all existing conditions. In addition to the above statement the Guarantee/Warranty Period shall include all labor cost related to all warranty work. 3. 1.1 GENERAL. As part of instruction for operating equipment, demonstrate the following procedures: Start up. product data and shall indicate applicable specification section and item numbers. Unless otherwise modified, provisions of General Conditions, Supplementary Conditions and Division-01 govern work under the Electrical Divisions. Mandatory Requirements: The following requirements are mandatory: Protective Equipment: Electricians must use full protective equipment (i.e., certified and tested insulating material to cover exposed energized electrical components, certified and tested insulated tools, etc.) Provide connectors with insulating bushings. unless otherwise noted. Section 16010 - General Electrical Requirements . New Construction: All new penetrations shall be provided with a pipe sleeve and sealant materials. ELECTRICAL GENERAL PROVISIONS . Calculations for battery capacity and voltage drop. SCOPE OF WORK . {s@_yj1' 3{J1tB;=6bcC. Installers' qualifications refer to the materials and methods required for the surface and building components being patched. B. <>>> Shop Drawings: pdf file format. endstream endobj startxref Arrange for chases, slots, and openings in building structure during progress of construction to allow for electrical installations. Include the following: Planned electrical systems layout, including conduit elbow radii and accessories. Refer to General Requirements of Division 01 for additional requirements pertaining to Submittals and Record Drawings. Any conduit abandoned in concrete slabs, walls, or other inaccessible locations shall be left with a nylon pull wire. 590 0 obj <>stream Refer to Division 01 Section "Definitions and Standards" for definition of "experienced Installer." The drawings and specifications shall be followed in layout of work. Compliance with the requirements of NFPA 70E is subject to ongoing inspection by University personnel and failure to comply will result in an immediate Stop Work order being issued and enforced at the contractors expense. COMAR (Code of Maryland Regulations). Conduit may remain to be reused for new work provided it is of the specified size and type and in condition acceptable to UMB. ph p hf h8 B* Div. For each electrical outage request include a photograph of the panel index schedule for each panel affected by the outage. +"Y3`pHw]|Gq{5ST>#;@ @FF hbbd``b` $Z ~BARD0 !LAF10t' 1.2 Page 1 of 4 REFERENCES .1 American National Standards Institute/Institute of Electrical and Electronics Engineers (ANSI/IEEE). Place grout to completely fill equipment bases. Install systems, materials, and equipment level and plumb, parallel and perpendicular to other building systems and components, where installed exposed in finished spaces. View Specification PDF - The Pennsylvania Turnpike. Clearances for servicing and maintaining electrical equipment. hb```b````a``eg@ ~f(0wPN A8.I.qk``Fx6I hVKk@+{la b64j[`KARh3Vd$U!XLa 'f:dM%wwc@%nyS^7-ZygHmnH"*pEK&xD,wb76I]VGm)Z_j@vUMmuyhxy S[{_T ,((n&+~z?h~YrM`%Rb$I"s?)s #: +}[6 #F7fWnV={RvRz&QQ A`5~o4lo SI*XU'wSB$5)|9D xb 1mfaqs7&YDE/q$"B" Afp|ISKCyd: C#S `IzLCoqw^`rSG7*V VF7A,.V4P l#o{# in9E^mj`PcuVd5 Provide the following, where applicable, in accordance with accepted trade standards and to Owners satisfaction: Replace damaged ceiling tiles. Install equipment and materials in existing structures. All work in Divisions 26, 27, and 28 shall comply with the latest version of following codes and regulations as adopted by the State of Maryland and the State Fire Marshal, unless otherwise specified. endstream endobj 1821 0 obj <>/Metadata 144 0 R/Outlines 346 0 R/Pages 1811 0 R/StructTreeRoot 599 0 R/Type/Catalog>> endobj 1822 0 obj <>/Font<>>>/Rotate 0/StructParents 0/Tabs/S/Type/Page>> endobj 1823 0 obj <>stream Also include the address, phone number and contact person for each supplier. Any work covered prior to any inspection in a manner which, in the inspector's opinion, precludes a complete inspection shall be uncovered at the installers cost. ANSI/EIA/TIA. B. The mark-ups shall be legibly marked in red pencil to show all changes and departures of the installation as compared with the original design. PART 1 - GENERAL . Maintenance agreements and similar continuing commitments. Fire rated wall and floor penetrations. You also have the option to opt-out of these cookies. afdb`dg4baTfX:r-X5)H! Conform to arrangements indicated by the Contract Documents, recognizing that portions of the Work are shown only in diagrammatic form. J{H5*aQDi!=GcN`H%{`8Zky:qr\a! 1912 0 obj <>stream endobj RELATED SECTIONS SECTION Title 14200 Conveiance System 16000 Electrical Works 16010 General Provisions for Electrical Work 16110 Raceways 16120 Conduits 16200 Cables and Wires 16300 Supporting Devices 16400 Main Distribution Equipment 16500 Lighting Install systems, materials, and equipment to conform with approved submittal data, to greatest extent possible. All such outages shall be performed on other than normal duty hours. 904 0 obj <>stream SUMMARY This Section includes general administrative and procedural requirements, as well as the following basic electrical materials and methods: Referenced organizations and codes Site visit Outages Installers qualifications Work performance Submittals Quality assurance Delivery storage and handling Sequencing and scheduling Variances Guarantee/warranty Listed manufacturers Approved equal equipment layouts Fire stops & smoke seals for wall & floor sleeve applications Coordination drawings Construction record documents Operation and Maintenance manuals electronic files Concrete housekeeping pads Grout Roughins Electrical installations. are not concealed by new work. Floor Pipe Sleeves Applications: Pipe sleeves are required for all new conduit risers passing through floor slabs. %%EOF UL (Underwriters Laboratories). Access shall be as required by code and/or as determined by the Architect and Engineer. Maintenance. Install systems, materials, and equipment giving right-of-way priority to systems required to be installed at a specified slope. Provide larger trim or cover plates for new devices, where old back boxes, holes, etc. TURF CLUB 16010-1 GENERAL PROVISIONS MASTER F:\WORDPROC\ZEIJOBS\883-001\16010 SECTION 16010 GENERAL PROVISIONS PART 1 - GENERAL Related Documents: Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 1 Specification sections, apply to this section. SECTION 16010 - GENERAL PROVISIONS 1.0 GENERAL CONDITIONS: All sections under this Division shall be subject to the requirements of the Architect's General Conditions - UAP Doc. PROJECT PUNCH OUT Architect/Engineer will perform punch out reviews and will provide the Contractor with a list of punch list items to be completed before contract close out. Follow supported equipment manufacturer's setting templates for anchor bolt and tie locations. 1 0 obj B. Obtain all necessary permits from c $ ) p@P ! xb```f``Z$31 P9&0`(*k^?f(]A 33$M?sOXiU>0seuA[!TC@EBt[lytx*%g K NZI9D&\m; ,fNgr\ r9T^LUYn~K6F.%ragg,n:a9id""$M])2bISPyb`6``:EZc `2p%KGS;^eNLM\|j P}e`N 0o2304@ KB Any defects in workmanship, materials, or performance which appear within the guarantee period shall be corrected by the contractor without cost to the owner, within a reasonable time, to be specified by UMB. Sequence, coordinate, and integrate installations of mechanical materials and equipment for efficient flow of the Work. Omission of words or phrases such as "the Contractor shall", "as shown on File Format: Coordination drawings shall be in a layered structure form as CAD Files or PDF Files for each floor with searchable text as follows: File Structure: The pdf or dwg files shall have separate layered structure for: Building Elements: Indicate each building element on separate layers, such as: Walls. @W|$" The hot work permit copy shall remain on the job site at the hot work location until such work is completed at which time the permit shall be returned to Environmental Health and Safety. endstream endobj 879 0 obj <. INSPECTIONS Contractor shall: Schedule, pay for (as applicable) and attend all inspections required by the Authorities Having Jurisdiction. ']xOs 0LSJ$C}q]7#y6t hs.%7fu 7~[2{& x ](>B|>LWwiy=>,?^": NESC (National Electrical Safety Code). 11275 0 obj <>/Filter/FlateDecode/ID[<1BCD9CA6C4893D4A874390606B4A9A2F>]/Index[11261 22]/Info 11260 0 R/Length 76/Prev 791633/Root 11262 0 R/Size 11283/Type/XRef/W[1 2 1]>>stream Patch, repair and repaint all walls and surfaces cut, penetrated or otherwise disturbed by the work. Necessary cookies are absolutely essential for the website to function properly. Coordination Effort: This coordination effort shall include detailing major elements, components, and systems of electrical equipment and materials in relationship with other systems, installations, and building components. o}B UJV5tM|w{&3cO*vnIg\6u(A2(^`h``h` @y40u@$X #X(Rp@1f Verify all dimensions by field measurements. Coordinate installation of identifying devices after completing covering and painting where devices are applied to surfaces. Control sequences. Provide at least forty (40) hours straight time instruction to the operating personnel. Remove and replace defective Work. RECORD DRAWINGS (As Built) Upon completion of the electrical installations, the Installer shall deliver to the Architect one (1) complete set of marked-up blueprints of the electrical contract drawings. CONCRETE HOUSEKEEPING PADS COORDINATE CONCRETE WORK WITH DIVISION 3. %PDF-1.5 % All submitted materials and equipment are subject to approval by the A/E and UMB. endstream endobj startxref Make all necessary investigations as to locations of utilities and all other matters which can affect the work. Prepare floor plans, elevations, and details to indicate penetrations in floors, walls, and ceilings and their relationship to other penetrations and installations. Submit the work permit with the outage request. Show all access doors for concealed junction boxes devices. Narrow Section Ball Bearings (16000, 16100). General: Construct concrete housekeeping pads to support mechanical equipment were indicated and as detailed on the drawings and as specified herein. For equipment requiring seasonal operation, perform instructions for other seasons at the same time. 0 Cleaning. Single row deep groove ball bearings are particularly versatile, have low friction and are optimized for low noise and low vibration, which enables high rotational speeds. Access panels and doors are specified in the Architectural Specifications. QUALITY ASSURANCE Comply with NFPA 70 for components and installation. Sizes and location of required concrete pads and bases. SECTION 16010 - GENERAL PROVISIONS SECTION INDEX 1.0 General Conditions 12.0 General Description 13.0 Work Included 24.0 Codes, Inspection, Permits and Fees 35.0 Record Drawings 36.0 Shop Drawings, Samples and Other Submittals 47.0 Coordination 58.0 Minor Modifications 59.0 Guarantee 6 10.0 Approvals, Substitutions, Etc. Motor manufacturer, motor type or model . Coordinate connection of electrical systems with exterior underground and overhead utilities and services. CUTTING, WELDING, BURNING Before the contractor and/or any sub-contractor commences any cutting, welding, burning or other type of hot work at UMB, the contractor shall contact the UMB Fire Marshals Office located @ 620 W. Lexington Street, 6th Floor, Room 6113 or by phone @ 1-410-706-3494 to obtain a hot work permit. stream [l*/ Deliver on the premises, where directed, existing material and equipment which is to be salvaged and remain property of Owner. 2013 0 obj <>/Filter/FlateDecode/ID[<7A92318D9A66904D9BE2AA2059D48142><9E5BD34DD47A4B4CACDF0D2F3CF07D4E>]/Index[2006 15]/Info 2005 0 R/Length 55/Prev 136060/Root 2007 0 R/Size 2021/Type/XRef/W[1 2 1]>>stream 4206 0 obj <>/Filter/FlateDecode/ID[<3C9B520689C7864B9A48B04B8892C8F0><70969F182CD17F458CE0C92FB6F87795>]/Index[4188 97]/Info 4187 0 R/Length 96/Prev 405976/Root 4189 0 R/Size 4285/Type/XRef/W[1 3 1]>>stream Section 16010 General Electrical Provisions Section 16120 Wire and Cables Section 16130 Wiring Devices Section 16160 Pilot Devices . BASIC ELECTRICAL REQUIREMENTS . Job No. [r'9}I!tn>oW KYa jRta4UIY3z$[gR%?F5r.jPSbei})lVZHk'vMTEJ|Agdd*z. Reimbursement shall be made by deducting the Architect/Engineer fee from the Contractor's final payment. Services include: Electrical penetrations include conduits and cables. Provide installation in accordance with recognized trade organizations and standards: NEMA. 4 | SECTION-16000 1.02 A. EU PRODUCT DIRECTIVES a) The EU Product Directives deal with large families of products or horizontal risks, such as those addressed in the Electromagnetic This instruction period shall consist of not less than five (5) eight (8) hour days. Div. Provide forms for placement of grout, as required. 0000005420 00000 n Hazards. Cutting, welding and burning Concrete housekeeping pads Grouting Protection of work Provisions for access Demonstration and instruction Equipment provided under another division or by others Record drawings Closeout procedures Inspections Demolition Repairs and restoration of surfaces and finishes Final cleaning Project punchout Summary of Work: Provide a complete integrated electrical system in accordance with the intent of these specifications and the accompanying drawings.